Outdoor Enclosures

SN-TC Telecom Container Series

Insulated Outdoor Telecommunications Container, IP54 / IP55

Overview

The SN-TC Telecom Container Series free-cooling build in a studio view with the front doors open: the fully welded steel body with its double-wall edge, cast ISO 1161 corner fittings at the base, lifting points on the structural frame, the all-metal door locks and a white louvered free-cooling ventilation grille on the side wall.
SN-TC with 5 numbered details, listed below the photo.

SN-TC Telecom Container Series is a range of insulated outdoor telecommunications containers available in 10 ft, 20 ft and 40 ft configurations, designed for the installation, protection and operation of telecommunications, power and monitoring equipment in demanding outdoor environments. The container features a double-wall construction with 100 mm mineral-wool insulation and an internal magnesite-board lining, reducing heat loss in cold weather and protecting the interior from excessive heating in summer. The container is built around a fully welded structural steel frame integrated with a reinforced base. The reinforced modular floor is designed to withstand a concentrated load of up to 1000 kg at any point and provides a stable foundation for installed equipment. ISO 1161 corner fittings built into the base allow transportation using equipment intended for standard ISO containers, while dedicated lifting points in the structural frame support crane lifting and rigging operations. Removable front doors with concealed hinges provide access to the interior. The doors are secured by heavy-duty vandal-resistant all-metal locks, with the locking mechanisms additionally protected by removable steel security covers. Depending on the required thermal load and operating conditions, the container can be configured with an air-conditioning system or a free-cooling system.

At a glance

Series
Telecom Container Series
Container Sizes
10 / 20 / 40 ft
Construction
Double-wall steel construction
Insulation & Lining
100 mm mineral wool + magnesite board
Climate System
Free Cooling or Air Conditioning, 6 / 8 / 10 kW
Access
Front doors
Mounting
Concrete foundation or steel support frame

Numbered details in the photo

  1. Double-Wall Construction Double-wall enclosure structure with mineral-wool insulation helps reduce heat loss in cold weather and limits excessive heating in summer.
  2. ISO Corner Fittings ISO corner fittings built into the base support handling and transport using equipment intended for standard ISO containers.
  3. Lifting Points Dedicated lifting points in the structural frame allow crane lifting and rigging operations.
  4. Vandal-Resistant Doors Removable doors with concealed hinges and protected all-metal locking mechanisms provide increased resistance to unauthorised access.
  5. Free-Cooling Ventilation Grille Ventilation grille forms part of the free-cooling air path, allowing outside air to be used for enclosure cooling when operating conditions permit.

Key figures

Container Sizes
10 / 20 / 40ft
Cooling Capacity
6 / 8 / 10kW
Ambient Range
−40…+60°C
Point Floor Load
Concentrated floor load up to 1000 kilograms at any point.
Protection
Ingress protection rating IP54 or IP55, depending on the climate system.

Key features

Applications, contents and accessories

Typical applications

  • Mobile Network Infrastructure
  • Wireless Communication Systems
  • Cable Television Networks
  • Digital Transmission Networks
  • Outdoor Telecommunications Nodes
  • Remote Communication Sites

Standard supply

  • Telecom Container Assembly
  • Climate System
  • Power Distribution Cabinet
  • Metering Cabinet
  • Lighting System
  • Monitoring System
  • Cable Tray System
  • Key Set
  • Technical Documentation

Compatible accessories

  • Floor-standing data cabinet for installation inside the container Floor-Standing Cabinet
  • Two-frame open rack for 19-inch equipment Open Rack
  • Fiber optic distribution frame for installation inside the container Fiber Optic Distribution Frame

Size and configuration matrix

Rows list the three container sizes — 10 ft, 20 ft and 40 ft. The row header gives the container size. Columns give external dimensions (width × height × length), climate system, cooling capacity, protection rating and net weight. Net weight is shown as the free-cooling build, then the air-conditioning build.
Model External Dimensions (W × H × L) (mm) Climate System Cooling Capacity (kW) Protection Rating Net Weight (F / AC) (kg)
10 ft 2430 × 2600 × 3000 mm Free Cooling / Air Conditioning 6 / 8 / 10 kW IP54 / IP55 1780 / 1830 kg
20 ft 2430 × 2600 × 6060 mm Free Cooling / Air Conditioning 6 / 8 / 10 kW IP54 / IP55 3650 / 3700 kg
40 ft 2430 × 2600 × 12200 mm Free Cooling / Air Conditioning 6 / 8 / 10 kW IP54 / IP55 7400 / 7450 kg

Overall dimensions include the projecting climate unit or free-cooling ventilation grille; see the technical drawings. Container lengths are the rounded ISO nominal values (3000 / 6060 / 12200 mm).

Technical drawings

Standard Equipment

Factory-installed equipment

Equipment fitted at the factory, with specification and quantity.
Item Specification Qty
Climate System Air-conditioning or free-cooling system, 6 / 8 / 10 kW depending on configuration 1 set
Metering Cabinet Factory-installed electrical metering assembly 1 pc
Power Distribution Cabinet Factory-installed power distribution and protection assembly 1 pc
Monitoring System Integrated monitoring and control system with local display and remote communication interfaces 1 set
Sensor Set Temperature, humidity, smoke, flood, door-opening and impact monitoring 1 set
Lighting System Internal container lighting system 1 set
Cable Tray System Perforated metal cable trays mounted on dedicated supports 1 set
Cable Entry System Cable glands and cable-entry provisions; configuration depends on container size 1 set
Grounding System Internal protective grounding and bonding system 1 set

Metering Cabinet — Components

Components of the factory-installed metering cabinet, with specification and quantity.
Component Specification Qty
Metering Box Electrical enclosure for metering components 1 pc
Energy Meter Electrical energy consumption metering 1 pc
Circuit Breaker 3P, 63 A 1 pc
Neutral Terminal N 1 pc

Power Distribution Cabinet — Components

Components of the factory-fitted 3U electrical control panel, with specification and quantity.
Component Specification Qty
Power Distribution Cabinet Enclosure DIN-rail distribution enclosure 1 pc
I-0-II Changeover Switch 3-position manual switch: I – 0 – II 1 pc
Phase Indicator Three-phase voltage presence indication 1 pc
Circuit Breaker 3P, 63 A 2 pcs
Circuit Breaker 3P, 32 A 1 pc
Circuit Breaker 3P, 25 A 1 pc
Circuit Breaker 1P, 16 A 1 pc
Circuit Breaker 1P, 6 A 3 pcs
Circuit Breaker 1P, 4 A 1 pc
Residual Current Device (RCD) 2P, 16 A, 30 mA, 6 kA 1 pc
DIN-Rail Schuko Socket 16 A 1 pc
DIN-Rail Power Supply Auxiliary DC power supply 1 pc
Feed-Through Terminal Blocks For internal electrical connections 3 pc
Neutral Terminal Block N 1 pc
PE Terminal Block PE 1 pc

Climate System — Technical Specifications

Technical specifications of the free-cooling and air-conditioning climate systems, side by side.
Parameter Free Cooling Air Conditioning
Climate System Type Open-type free cooling Industrial-type air conditioning
Cooling Capacity 6 / 8 / 10 kW 6 / 8 / 10 kW
Power Supply 220–230 V AC 220–230 V AC
Maintained Internal Temperature +5…+45 °C +5…+35 °C
Ambient Operating Range −40…+60 °C −40…+60 °C
Maximum Relative Humidity Up to 98% @ +35 °C, non-condensing Up to 98% @ +35 °C, non-condensing
Cooling Principle Outside-air cooling Mechanical refrigeration cooling
Control System Integrated climate controller Integrated climate controller
Monitoring Integration Temperature, humidity and alarm monitoring Temperature, humidity and alarm monitoring

Monitoring & Control System — Technical Specifications

Technical specifications of the integrated monitoring and control system.
Parameter Specification
System Functions Remote monitoring, climate-system control, sensor data acquisition, alarm processing and event logging
Climate System Compatibility Free Cooling / Air Conditioning
Local Interface Touch display
Temperature Sensor Inputs 5
Humidity Sensor Inputs 5
Discrete Sensor Inputs 6
Discrete Sensor Configuration Smoke, flood, door opening, impact + 2 reserve inputs
Sensor Interface 1-Wire
Digital Interfaces 2 × RS485
PWM Channels 2
Network Interface Ethernet
Web Interface Built-in web server
Software Interface REST
Network Protocols HTTPS, HTTP, IPv4
Monitoring Protocols SNMPv2c, SNMPv3
Alarm Notification SNMP trap
Event Database 10,000 events

Optional equipment and systems

Optional equipment and systems available for this enclosure, grouped by function.
Group Includes
Power Distribution & Protection Additional circuit breakers, surge protection modules, sockets, generator inlet connectors, PDUs
Backup Power UPS systems, DC power systems, battery systems
Safety & Fire Protection Smoke detection expansion, fire alarm equipment, automatic fire suppression systems
Monitoring & Access Control Additional sensors, remote I/O modules, access-control systems, additional door monitoring
Equipment Installation Systems 19-inch racks, mounting frames, equipment supports, additional cable-management systems

Reference Standards

Standards are listed as design and application references and do not constitute third-party product certification unless explicitly stated.

Colour and ordering

Available finishes

Ordering code

SN-TC-[SIZE]FT-[kW]-[CLIMATE]

[SIZE]FT
Container size by external length in feet — 10FT, 20FT, 40FT
[kW]
Cooling capacity in kilowatts — 6, 8, 10
[CLIMATE]
Climate system: AC for the air-conditioning system, F for the free-cooling system — AC, F

Example SN-TC-20FT-10-AC 20-foot Telecom Container Series enclosure, 10 kW cooling capacity, air-conditioning system, RAL 7035, IP55.

There are no colour options.