Outdoor Enclosures
SN-THERMA Air-Conditioned Series
Outdoor Floor-Standing Enclosure, IP55
Overview
SN-THERMA / SN-THERMA MAX Air-Conditioned Series is a range of double-wall steel outdoor floor-standing enclosures designed for the installation and protection of 19-inch telecommunications equipment. The double-wall construction with non-combustible A1-class mineral-wool insulation reduces heat loss in cold weather and protects the enclosure interior from excessive heating in summer. A door-mounted closed-loop climate unit — compressor air conditioning with an air-to-air heat exchanger and an integrated heater — provides active temperature control without exchanging cabinet air with the environment. Front and rear doors provide convenient access to installed equipment. Two pairs of adjustable 19-inch mounting rails allow the mounting depth to be adapted to the installed equipment. The enclosure is equipped with a removable roof and a reinforced floor plinth. SN-THERMA MAX provides increased cabinet depth for installations requiring additional internal space.
At a glance
- Series
- Air-Conditioned Series
- Models
- Models SN-THERMA 34U, 38U and 42U, one air-conditioning unit; and SN-THERMA MAX 34U, 38U and 42U, one air-conditioning unit
- Usable rack space
- 34U / 38U / 42U
- Construction
- Double-wall steel, A1 mineral-wool insulation
- Access
- Front and rear doors
- Climate control
- Closed-loop air conditioning + integrated heater
- Mounting
- Concrete foundation or support frame
Numbered details in the photo
- Air Conditioner Door-mounted closed-loop climate unit with compressor cooling, an air-to-air heat exchanger and an integrated heater.
- 19″ Mounting Rails Two pairs of adjustable rails allow the mounting depth to match the installed equipment.
- Double-Wall Body Double-wall steel construction with A1-class mineral-wool insulation.
- Removable Roof The roof projects beyond the cabinet body and is supplied separately to reduce transit damage.
- Floor Plinth Fixing holes in the plinth allow the enclosure to be secured to a concrete foundation using suitable anchors.
Key figures
- Height
- 34, 38 or 42 rack units
- Width
- 830mm
- Depth
- Cabinet body depth 825 millimetres for SN-THERMA, 1175 for SN-THERMA MAX
- Static Load
- Static load 800 kilograms
- Protection
- Ingress protection rating IP55
Key features
-
Double-Wall Steel Construction
Inner and outer steel shells provide a robust insulated enclosure structure.
-
A1 Mineral-Wool Insulation
Non-combustible insulation reduces heat loss in cold weather and limits heating in summer.
-
Closed-Loop Air Conditioning
Integrated air-conditioning system provides compressor cooling and free-cooling operation without direct exchange of cabinet air with the environment.
-
Integrated Heater
Heater integrated into the air-conditioning unit supports operation at low ambient temperatures.
-
19″ Mounting Rails
Two pairs of 19-inch mounting rails with depth adjustment in 25 mm increments.
-
Three-Point Locking System
Five-bolt lever lock with upper and lower locking rods secures the door at three points.
-
Floor Plinth with Fixing Holes
Fixing holes allow anchoring to a concrete foundation; removable access covers provide additional cable access through the plinth.
-
Front & Rear Access
Front and rear doors provide convenient access to installed equipment from both sides.
Applications, contents and accessories
Typical applications
- Mobile Network Infrastructure
- Wireless Communication Systems
- Cable Television Networks
- Digital Transmission Networks
- Outdoor Telecommunications Nodes
- Remote Communication Sites
What's in the box
- 19″ Mounting Rails
- Mounting Rail Support Brackets
- Electrical Control Panel
- Air-Conditioning Unit
- Cable Entry Panels
- Door Opening Sensor
- Removable Roof
- Floor Plinth
- Protective Steel Cover for Air Conditioner
- Grounding Busbar
- 2 key sets — one set for each lock
- Set of Eye Bolts
- Technical Documentation
Compatible accessories
-
Cable ring organizer
-
Shelf
-
3U Electrical Distribution Panel
Size and configuration matrix
| Model | Usable Rack Space (U) | Total Rack Capacity (U) | External Height (mm) | Cabinet Body Width (mm) | Cabinet Body Depth (mm) | Usable Mounting Depth (mm) | Net Weight (kg) |
|---|---|---|---|---|---|---|---|
| SN-THERMA-FS-WD-19-34U-083-083-1C | 34 U | 34 U | 1769 mm | 830 mm | 825 mm | 450 mm | 270.0 kg |
| SN-THERMA-FS-WD-19-38U-083-083-1C | 38 U | 38 U | 1947 mm | 830 mm | 825 mm | 450 mm | 278.0 kg |
| SN-THERMA-FS-WD-19-42U-083-083-1C | 42 U | 42 U | 2125 mm | 830 mm | 825 mm | 450 mm | 286.0 kg |
| SN-THERMA-MAX-FS-WD-19-34U-083-117-1C | 34 U | 34 U | 1769 mm | 830 mm | 1175 mm | 800 mm | 320.0 kg |
| SN-THERMA-MAX-FS-WD-19-38U-083-117-1C | 38 U | 38 U | 1947 mm | 830 mm | 1175 mm | 800 mm | 328.0 kg |
| SN-THERMA-MAX-FS-WD-19-42U-083-117-1C | 42 U | 42 U | 2125 mm | 830 mm | 1175 mm | 800 mm | 336.0 kg |
The removable roof and the door-mounted air conditioner project beyond the cabinet body; overall dimensions including these external components are shown in the technical drawings. Net weight includes the removable roof. The removable roof is supplied separately from the enclosure body to reduce the risk of damage during transportation.
Technical drawings
-
Front View
Full description of this drawing
Front elevation, generic for all models. Cabinet body width 830 mm; roof overhang width 850 mm; plinth width 795 mm; roof slope 15°. Rail spacing 450 mm (19-inch). Front and rear doors.
-
Side View
Full description of this drawing
Side elevation. Cabinet body depth 825 mm (SN-THERMA) or 1175 mm (SN-THERMA MAX); depth including the roof 875 / 1225 mm; the door air conditioner adds a further 100 mm. Rail depth adjustable in 25 mm steps. Base cable entry panel: PG16-3, PG9-8, PG21-9.
-
Top View — Roof Removed
Full description of this drawing
Top-down view with the removable roof lifted off, generic for all models, showing the base cable entry panel and the mounting-depth clearance. Base cable entry panel fitted with PG13.5 (10) and PG21 (10) glands. Usable mounting depth 450 mm (SN-THERMA) or 800 mm (SN-THERMA MAX), with 70 mm front and 125 mm rear clearance as marked.
-
General View
Full description of this drawing
General view with the removable roof lifted off, one side panel and the door removed. The frame, the two pairs of 19-inch mounting rails, the base cable entry panel and the floor plinth are visible.
Standard Equipment
Factory-installed equipment
| Item | Specification | Qty |
|---|---|---|
| Air-Conditioning Unit | 1500 W @ L35/L35, 230 V AC | 1 pc |
| Protective Steel Cover for Air Conditioner | External steel cover for additional mechanical protection of the air-conditioning unit | 1 pc |
| Door Opening Sensors | Magnetic reed contact sensor | 2 pcs |
| Side Cable Entry Panel | Fitted with 20 cable glands: 8 × PG9, 3 × PG16, 9 × PG21 | 1 pc |
| Base Cable Entry Panels | Each panel fitted with 20 cable glands: 10 × PG13.5, 10 × PG21 | 2 pcs |
| Electrical Control Panel | Side-mounted; does not occupy rack units | 1 pc |
| Document Pocket | Metal document pocket mounted on the inside of the door; suitable for A4 documents | 1 pc |
| Grounding Busbar | Copper grounding busbar with 6 connection points, mounted on 2 insulated supports | 1 pc |
Electrical Control Panel
| Component | Specification | Qty |
|---|---|---|
| Circuit Breaker | 3P, 32 A | 1 pc |
| Circuit Breaker | 1P, 16 A | 1 pc |
| Residual Current Device | 2P, 25 A, 30 mA | 1 pc |
| Circuit Breaker | 1P, 6 A | 2 pcs |
| DIN-Rail Schuko Socket | 16 A, 230 V AC | 2 pcs |
| DIN-Rail Neutral Busbar | Insulated, 6 × 9 mm, 10 terminals | 1 pc |
| DIN-Rail PE Busbar | Insulated, 6 × 9 mm, 10 terminals | 1 pc |
Air-Conditioning Unit — Technical Specifications
| Parameter | Specification |
|---|---|
| Cooling Capacity | 1500 W @ L35/L35 |
| Cooling Capacity | 1100 W @ L35/L55 |
| Heat Exchange Capacity | 80 W/K |
| Heater Power | 1000 W |
| Internal Airflow | 450 m³/h |
| Air-Conditioning Power Supply | 230 V AC, 50 Hz |
| Heat-Exchanger Power Supply | 48 V DC |
| Cooling Operating Range | −15…+55 °C |
| Heat-Exchange External Temperature Range | −40…+55 °C |
| Communication Interface | RS485 |
| Communication Protocol | Modbus RTU |
| Protection Rating | IP55 |
| Refrigerant | R134a |
Optional equipment and systems
| Group | Includes |
|---|---|
| Sensors & Monitoring | Flood sensors, smoke sensors, vibration sensors, monitoring systems |
| Safety Systems | Door status monitoring, alarm signalling devices |
| Power Distribution & Protection | Additional circuit breakers, surge protection modules, sockets, generator inlet connectors, PDUs |
| Backup Power | Power supply systems, batteries |
Standards and certification
- 2014/35/EU Low Voltage Directive
- 2014/30/EU Electromagnetic Compatibility Directive
- EN 60529:1991/A2:2013/AC:2019-02 Degrees of protection provided by enclosures (IP code)
- EN 61439-1:2011 Low-voltage switchgear and controlgear assemblies — general rules
- EN 61439-3:2012/AC:2019-04 Distribution boards intended to be operated by ordinary persons
- EN 62368-1:2014/AC:2015 Audio/video, information and communication technology equipment — safety
Colour and ordering
Available finishes
- RAL 7035 Light grey
Ordering code
SN-THERMA[-MAX]-FS-WD-19-[U]U-083-[D]-1C
SN-THERMA- Series name
[-MAX]- Omit for SN-THERMA (825 mm body depth); include for SN-THERMA MAX (1175 mm body depth, 800 mm usable mounting depth)
FS- Floor-standing
WD- Welded construction
19- 19-inch rack standard
[U]- Rack height in rack units (usable space equals total capacity) — 34, 38, 42
083- Width code — 830 mm
[D]- Depth code — 083 for SN-THERMA (825 mm body), 117 for SN-THERMA MAX (1175 mm body)
1C- One air-conditioning unit
Example
SN-THERMA-MAX-FS-WD-19-42U-083-117-1C
Air-Conditioned Series outdoor floor-standing enclosure, MAX depth (1175 mm body, 800 mm usable mounting depth), 42 rack units, one air-conditioning unit, RAL 7035, IP55.
Width is fixed at 830 mm; SN-THERMA MAX differs only in body depth and usable mounting depth. There are no colour options.